  • Abstract
    This paper presents a comparison of two of the most sensitive methods to detect low-level turn-to-turn faults in the windings of three-phase transformers. The performance of the negative sequence component and of the space vector protection algorithms is tested under several internal and/or external fault conditions. The simulation results indicate that the fault detection sensitivity of both methods is very similar.
  • Keywords
    "Circuit faults","Power transformers","Windings","Sensitivity","Relays","Current transformers","Computational modeling"