  • Abstract
    Double-conversion UPS provide top protection to critical loads, but limited efficiency. However, such UPS often support alternative high-efficiency operating modes (e.g. so-called ECO Mode). This paper discusses Active ECO Mode operation, introducing Active Damping Control for improving Power Quality with minimal losses. The system evolves into a Multi-Mode UPS, where the operating mode is selected for optimal trade-off between power conditioning and efficiency. Performance improvement is confirmed by experimental results and field experience.
  • Keywords
    "Uninterruptible power systems","Power harmonic filters","Reactive power","Inverters","Harmonic analysis","Rectifiers","Damping"