DocumentCode
3678822
Title
Active damping control of multi-mode UPS for power quality improvement
Author
Lorenzo Giuntini
Author_Institution
GE CRITICAL POWER, Via Cantonale, 50, Riazzino, Switzerland
fYear
2015
Firstpage
1
Lastpage
10
Abstract
Double-conversion UPS provide top protection to critical loads, but limited efficiency. However, such UPS often support alternative high-efficiency operating modes (e.g. so-called ECO Mode). This paper discusses Active ECO Mode operation, introducing Active Damping Control for improving Power Quality with minimal losses. The system evolves into a Multi-Mode UPS, where the operating mode is selected for optimal trade-off between power conditioning and efficiency. Performance improvement is confirmed by experimental results and field experience.
Keywords
"Uninterruptible power systems","Power harmonic filters","Reactive power","Inverters","Harmonic analysis","Rectifiers","Damping"
Publisher
ieee
Conference_Titel
Power Electronics and Applications (EPE´15 ECCE-Europe), 2015 17th European Conference on
Type
conf
DOI
10.1109/EPE.2015.7309203
Filename
7309203