Title :
PD pattern recognition in Metal-clad switchgear by using UHF technology
Author :
Dohoon Lee;Jinho Lee;Jong-Woong Choe;Seok-Weon Park;Young-Kun Kim
Author_Institution :
LS Industrial systems, Chungcheongbuk-do, Korea
Abstract :
It is important to ensure the operational safety of the MCSG because The Metal clad switchgear plays a great role in ensuring the reliability of power supply. For that reason, many researchers develop various methods to diagnose its condition by using TEV, HFCT, Coupling capacitor, UHF. In spite of this effort, Unexpected MCSG failures continue to happen often resulting in catastrophic equipment damage. In this paper, four artificial insulation defect models were designed to generate UHF PD signals, which were installed in the 7.2kV MCSG and detected by a UHF antenna. For the classifying and analyzing the PD signal, an optimized algorithm was used in the MSCG diagnosis system. This work will be contributed to develop Advanced Diagnosis & preventive system for MCSG.
Keywords :
"Partial discharges","Switchgear","Discharges (electric)","Insulation","UHF antennas","Noise measurement","Corona"
Conference_Titel :
Electric Power Equipment ? Switching Technology (ICEPE-ST), 2015 3rd International Conference on
DOI :
10.1109/ICEPE-ST.2015.7368433