Asymmetrical fault ride-through characteristic of dual stator-winding induction generator wind power system
Author :
Kai Shi; Zengqiang Wan; Peifeng Xu; Kerong Liu
Author_Institution :
Sch. of Electr. &
fYear :
2015
Firstpage :
1059
Lastpage :
1062
Abstract :
Analysis on operation characteristics of dual stator-winding induction generator (DWIG) wind power system under asymmetrical grid faults is elaborated in detail in the paper. The output dc voltage is maintained steady by the rapid flux-weakening control by the static excitation controller (SEC) on the control-winding side. Fault ride through operation is achieved by restraining input power from dc side and avoiding fluctuations with 2 times the grid frequency during asymmetric faults happen. Simulation results prove that DWIG wind power system has strong fault-ride-through capability without additional hardware equipment whether single phase or two phase grid asymmetric grid voltage drop.
Keywords :
"Stators","Induction generators","Wind power generation","Power system stability","Voltage control","Fluctuations","Time-frequency analysis"