• DocumentCode
    3760403
  • Title

    Development and experiment of fast breaker-type fault current limiter

  • Author

    Feng Gao;Shaogui Ai;Ran Ding;Yongning Huang

  • Author_Institution
    Ningxia Electric Power Research Institute, State Grid Ningxia Electric Power Company, Yinchuan, China
  • fYear
    2015
  • Firstpage
    1790
  • Lastpage
    1794
  • Abstract
    Fault current limiter (FCL) is one of the efficient technological measures to solve the increasingly serious problem of excessive short-circuit current in power grid. A fast breaker-type fault current limiter with modularized design is developed on the basis of 12kV fast-speed vacuum breakers and short-circuit current perfect forecast and zero-cross point precise phase controlled breaking technologies. Zero-loss of the FCL is obtained under normal condition and up to 80 kA short-circuit current could be limited within 20ms to the safe breaking level of the system circuit breaker. The security, efficiency and reliability of the device are verified by field operation and two single-phase transient short-circuit experiment in a 330 kV network.
  • Keywords
    "Short-circuit currents","Limiting","Inductors","Circuit breakers","Decision support systems","Power industry","Current limiters"
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
  • Type

    conf

  • DOI
    10.1109/DRPT.2015.7432533
  • Filename
    7432533