• DocumentCode
    3762689
  • Title

    Harmonic current elimination in industrial power systems

  • Author

    Deria Pravitasari;Eka Firmansyah;T. Haryono

  • Author_Institution
    Department of Electrical Engineering and Information Technology, Gadjah Mada University, Grafika 2, Yogyakarta 55281, Indonesia
  • fYear
    2015
  • Firstpage
    358
  • Lastpage
    362
  • Abstract
    This paper discusses the elimination of harmonic currents in the industrial power system utilizing adjustable speed drives. The harmonic current pattern measured and simulation results will be compared to IEEE-Std 519-2014. ASD can generate harmonic currents caused by front-end or input rectifier which tends to draw in the form of non-sinusoidal currents and not continuous. Based on the measurement data THDi value reached 686.53%, IRMS at 928.75A and Ifund at 1285.6 A in one phase. Although the value THDi once installed filters still shows the %THDi value above the standard allowable value, this may be evidence that the LC filter can be used to eliminate harmonic currents on adjustable speed drives.
  • Keywords
    "Power harmonic filters","Harmonic analysis","Passive filters","Variable speed drives","Harmonic distortion","Capacitors"
  • Publisher
    ieee
  • Conference_Titel
    Information Technology, Computer, and Electrical Engineering (ICITACEE), 2015 2nd International Conference on
  • Print_ISBN
    978-1-4799-9861-6
  • Type

    conf

  • DOI
    10.1109/ICITACEE.2015.7437829
  • Filename
    7437829