Title :
Harmonic current elimination in industrial power systems
Author :
Deria Pravitasari;Eka Firmansyah;T. Haryono
Author_Institution :
Department of Electrical Engineering and Information Technology, Gadjah Mada University, Grafika 2, Yogyakarta 55281, Indonesia
Abstract :
This paper discusses the elimination of harmonic currents in the industrial power system utilizing adjustable speed drives. The harmonic current pattern measured and simulation results will be compared to IEEE-Std 519-2014. ASD can generate harmonic currents caused by front-end or input rectifier which tends to draw in the form of non-sinusoidal currents and not continuous. Based on the measurement data THDi value reached 686.53%, IRMS at 928.75A and Ifund at 1285.6 A in one phase. Although the value THDi once installed filters still shows the %THDi value above the standard allowable value, this may be evidence that the LC filter can be used to eliminate harmonic currents on adjustable speed drives.
Keywords :
"Power harmonic filters","Harmonic analysis","Passive filters","Variable speed drives","Harmonic distortion","Capacitors"
Conference_Titel :
Information Technology, Computer, and Electrical Engineering (ICITACEE), 2015 2nd International Conference on
Print_ISBN :
978-1-4799-9861-6
DOI :
10.1109/ICITACEE.2015.7437829