• DocumentCode
    3763009
  • Title

    Overhead transmission line sag, tension and length calculation using affine arithmetic

  • Author

    Yoseph Mekonnen Abebe;P. Mallikarjuna Rao

  • Author_Institution
    Department of Electrical Engineering, College of Engineering (A), Andhra University, Visakhapatnam-530 000, A.P, India
  • fYear
    2015
  • Firstpage
    211
  • Lastpage
    216
  • Abstract
    Transmission line sag, tension and conductor length varies with the variation of temperature due to thermal expansion and elastic elongation. Beside thermal effect, wind pressure and ice accumulation creates a horizontal and vertical loading on the conductor respectively. Such changes make the calculated data uncertain and require an uncertainty model. A novel affine arithmetic (AA) based transmission line sag, tension and conductor length calculation for parabolic curve is proposed and the proposed method is tested for different test cases. The results are compared with Monte Carlo (MC) and interval arithmetic (IA) methods. The AA based result gives a more conservative bound than MC and IA method in all the cases.
  • Keywords
    "Conductors","Temperature measurement","Transmission line measurements","Power transmission lines","Measurement uncertainty","Temperature","Ice"
  • Publisher
    ieee
  • Conference_Titel
    Power, Communication and Information Technology Conference (PCITC), 2015 IEEE
  • Type

    conf

  • DOI
    10.1109/PCITC.2015.7438162
  • Filename
    7438162