  • Abstract
    Gas insulated substations (GIS) are widely used as important switchgear equipment because of its highly reliable, low space requirement, the risk factor is low and easy to maintenance, yet some failures have been reported. Some of the failures are due to the presence of metallic particles inside the GIS compartment. The defect can be generated in GIS during production, maintenance, installation and due to ageing of the component. The ultra high frequency (UHF) method is used to diagnose the insulation condition of GIS by detecting the PD signals in GIS. This paper identifies PD patterns for free moving particle defect and particle fixed on cone using UHF method. As insulation failure usually starts with PD activity, this paper investigates the differences in PD characteristics in SF6 gas with different types of defects. Experimental results show that correct identification of defects can be achieved based on considered PD characteristics. The method can be applied to prove the quality of assembly work at commissioning, also on a regular basis after many years in service to detect aged and conducting particles as a part of the condition based maintenance.
  • Keywords
    "Partial discharges","UHF measurements","Gas insulation","Atmospheric measurements","Particle measurements","Sensors","Sensitivity"
  • Publisher
    ieee
  • Conference_Titel
    Condition Assessment Techniques in Electrical Systems (CATCON), 2015 International Conference on
  • Type

    conf

  • DOI
    10.1109/CATCON.2015.7449508
  • Filename
    7449508