DocumentCode :
3772563
Title :
Factors affecting the breakdown strength of transformer oil
Author :
William R. Bell;Michalis Danikas
Author_Institution :
Department of Electrical and Electronic Engineering, University of Newcastle upon Tyne, NE1 7RU, U.K.
fYear :
1982
fDate :
6/1/1982 12:00:00 AM
Firstpage :
264
Lastpage :
267
Abstract :
The a. c. breakdown strength of technical grade transformer oil is dependent on many factors. Some of the factors which have been studied in this paper are the effect of electrode area for brass and steel electrodes, the effect of gap spacing and the effect of oil velocity in the uniform field region (up to a few cm.sec?1). The phenomenon of spark conditioning has also been examined especially the effect of test cell capacitance. A few experiments have also been carried out to measure the effect of added contamination.
Keywords :
"Electrodes","Sparks","Steel","Oil insulation","Discharges (electric)","Impurities"
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1982 IEEE International Conference on
Print_ISBN :
978-1-5090-3123-8
Type :
conf
DOI :
10.1109/EIC.1982.7464485
Filename :
7464485
Link To Document :
بازگشت