Title :
Indoor and outdoor transformer insulation systems
Author :
W. W. Pendleton;Alfons Bimbiris
Author_Institution :
Anaconda Wire and Cable Company, Muskegon, Michigan
Abstract :
The thermal life studies are presented on a number of transformer insulation systems for equipment up to 500 KVA. Thermal classifications from 105 to 220 C are covered. The data is compiled from transformer models (transformerettes) using IEEE #117 techniques (developed for motorettes) modified for indoor and outdoor transformer conditions as approved by Underwriters´ Laboratories who recognized the classifications following submission of the data. Both copper and aluminum conductors are evaluated. These evaluations apply to both pad mount installations and underground residential distribution systems for both indoor and outdoor exposures.
Keywords :
"Insulation","Wires","Conductors","Copper","Power transformer insulation","Aging","Polyimides"
Conference_Titel :
Electrical Insulation Conference, 1973 EIC 11th
Print_ISBN :
978-1-5090-3110-8
DOI :
10.1109/EIC.1973.7468671