• DocumentCode
    379686
  • Title

    3D-MoM analysis of radio frequency noise radiation from HVDC converter station

  • Author

    Tanabe, Shinji ; Murata, Yuichiro ; Chishaki, Hirokazu ; Shimato, Toshiaki

  • Author_Institution
    Mitsubishi Electr. Corp., Hyogo, Japan
  • Volume
    2
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    534
  • Abstract
    Radiation of radio frequency noise from power transmission lines has been analyzed using a three dimensional method of moments (MoM) considering towers and buildings at a DC-to-AC converter station. The towers and the buildings reflect the electromagnetic waves. A 1/400-scale reduction model of the station has been fabricated for measurements to confirm the MoM analysis. Both results were confirmed by the measurements on site, and have a good agreement in the electromagnetic field distribution
  • Keywords
    DC-AC power convertors; HVDC power convertors; electromagnetic wave reflection; method of moments; radiofrequency interference; substations; thyristor convertors; 1.4 GW; 16 m; 23 m; 250 kV; 3D-MoM analysis; 400 m; 88 m; DC-to-AC converter station; HVDC converter station; buildings; electromagnetic field distribution; electromagnetic waves reflection; power transmission lines; radio frequency noise radiation; three dimensional method of moments; thyristor valve noise source; towers; Electromagnetic fields; Electromagnetic measurements; HVDC transmission; Message-oriented middleware; Noise reduction; Poles and towers; Radio frequency; Thyristors; Valves; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Conversion Conference, 2002. PCC-Osaka 2002. Proceedings of the
  • Conference_Location
    Osaka
  • Print_ISBN
    0-7803-7156-9
  • Type

    conf

  • DOI
    10.1109/PCC.2002.997573
  • Filename
    997573