Title :
An approach to the optimum insulation design of GCB interrupter
Author :
Nishikawa, S. ; Osawa, N. ; Yoshioka, Y.
Author_Institution :
Dept. of Electr. Eng., Kanazawa Inst. of Technol., Ishikawa, Japan
Volume :
3
fYear :
2002
fDate :
2002
Firstpage :
1640
Abstract :
The optimum dielectric design of gas circuit breakers (GCB) in a consistent design philosophy is described. Many electric field calculations were carried out on 3 GCB models and the relation between the key design parameters such as distance between tank and shield, major radius of shield electrode and full open distance were analyzed. As a result, it was found that there is a minimum curve in the relation between full open distance and the electric field strength. Using this minimum curve and the allowable electric field strength, we can design the optimum GCB structure. It is also shown, as an example, how to design the optimum GCB of 300 kV by using 3 GCB models.
Keywords :
electric fields; gas blast circuit breakers; gaseous insulation; interrupters; 300 kV; GCB interrupter; electric field calculations; full open distance; optimum insulation design; shield electrode major radius; tank to shield distance; Circuit breakers; Data analysis; Design engineering; Dielectrics and electrical insulation; Electrodes; Interrupters; Manufacturing; Shape; Student members; Voltage;