• DocumentCode
    3850135
  • Title

    Influence of the conductor temperature error on the overhead line ampacity monitoring systems

  • Author

    I. Albizu;E. Fernandez;A.J. Mazon;J. Bengoechea

  • Author_Institution
    Electrical Engineering Department, University of the Basque Country UPV/EHU, Faculty of Engineering of Bilbao
  • Volume
    5
  • Issue
    4
  • fYear
    2011
  • fDate
    4/1/2011 12:00:00 AM
  • Firstpage
    440
  • Lastpage
    447
  • Abstract
    Many real-time overhead line ampacity monitoring systems are based on the calculation of wind speed. The wind speed is obtained from the conductor temperature. The conductor temperature can be measured directly or it can be obtained indirectly from other magnitudes such as the tension or the sag. An error in the temperature difference gives as a result an error in the calculated wind speed and ampacity values. This study analyses and quantifies the influence of the temperature difference error in the obtained ampacity value. As a result, a method for the evaluation and the correction of the ampacity error that can be used in the monitoring systems is proposed.
  • Journal_Title
    IET Generation, Transmission & Distribution
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd.2010.0470
  • Filename
    5739621