    Current Limiting and Recovery Tests Under Load of Three-Phase Transformer Type Coaxial SFCL in a Model Power System

  • Author

    Yamabe, K. ; Yonemura, N. ; Shirai, Yasuyuki ; Baba, J.

  • Author_Institution
    Dept. of Energy Sci. & Technol., Kyoto Univ., Kyoto, Japan
  • Volume
    24
  • Issue
    3
  • fYear
    2014
  • fDate
    Jun-14
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Superconducting Fault Current Limiters (SFCLs) are expected to be installed in the power system for improving their reliability and stability. The three-phase transformer type coaxial SFCL with rewound structure have been proposed and designed in the past. Due to the rewound structure, internal magnetic field of an SFCL is cancelled and each phase of the SFCL can work independently without interference with the other coaxial phases. This paper describes current limiting performance and recovery characteristics in Recovery Under Load (RUL) operation of the proposed SFCL. The operation tests of the SFCL under load were carried out on a lab-scale model power system (one generator, double-circuit transmission line, and infinite bus system). In this system, faults occurred on one line. The SFCL was installed in the generator terminal in series and the generator continued to supply power to another line through the SFCL in fault sequence so the SFCL operated in RUL. It was confirmed that the SFCL limited the fault current from approximately 600 to 250 A, reduced the burden of the generator, and successfully recovered to superconducting state.
  • Keywords
    power system reliability; power system stability; power transformer testing; superconducting fault current limiters; current limiting test; double-circuit transmission line; infinite bus system); internal magnetic field; lab-scale model power system; model power system; power system reliability; power system stability; recovery test; recovery under load operation; rewound structure; superconducting fault current limiters; three-phase transformer type coaxial SFCL; Bismuth compounds; Circuit faults; Coils; Fault currents; Generators; Limiting; Superconducting transmission lines; BSCCO wire; rewound structure; superconducting fault current limiter (SFCL); transformer type;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/TASC.2013.2284543
  • Filename
    6620947