Potential harmonic iumpact of microturbines on a commercial power distribution system
Author
Kirawanich, Phumin ; O´Connell, Robert M.
Author_Institution
Dept. of Electr. Eng., Missouri Univ., Columbia, MO, USA
Volume
2
fYear
2003
fDate
13-17 July 2003
Abstract
ATP-EMTP Simulations of a 3-phase commercial power distribution system containing 250 kW, 480 V microturbines for distributed generation are described. The purpose of the simulations was to investigate the extent to which the nonlinear currents generated by the microturbines might cause line voltage distortion. The results showed that even at the most vulnerable lateral tap points in the system under worst-case conditions the voltage THD did not exceed the IEEE Standard 519 limitation for up to 40% saturation of commercial service entrances with microturbines.
Keywords
EMTP; distributed power generation; distribution networks; gas turbines; harmonic distortion; power system harmonics; turbogenerators; 480 V; EMTP; IEEE Standard 519 limitation; THD; commercial power distribution system; distributed generation; harmonic current; harmonic impact; microturbine generator; nonlinear current; voltage distortion; Circuit simulation; Distributed power generation; Impedance; Power distribution; Power generation; Power generation economics; Power system harmonics; Substations; Turbines; Voltage;