DocumentCode
413172
Title
Quality assurance after transformer refurbishment by means of polarisation depolarisation currents analysis
Author
Bhumiwat, Supatra A. ; Stattmann, Peter
Author_Institution
KEA Consultant, Auckland, New Zealand
Volume
2
fYear
2003
fDate
23-26 June 2003
Abstract
This work presents the result of polarisation depolarisation currents (PDC) analysis on two identical 10 MVA, 132/66-33/11 kV, 3φ separate-winding transformers after on-site refurbishment. It intends to show the achievement of the process in the form of dielectric properties evaluated by this new diagnostic tool. The paper demonstrates how the quality of oil and paper between each pair of windings can be assured by the technique.
Keywords
capacitance; dielectric polarisation; electric current measurement; insulation testing; power transformer insulation; transformer oil; transformer windings; 10 MVA; 11 kV; 132 kV; 66 to 33 kV; capacitance; dielectric properties; dissipation factor; insulation resistance; oil conductivity; oil quality; paper quality; polarisation depolarisation current analysis; polarisation index; quality assurance; recovery voltage; transformer refurbishment; winding transformers; Conductivity; Current measurement; Moisture; Oil insulation; Optical polarization; Petroleum; Power transformer insulation; Quality assurance; Substations; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech Conference Proceedings, 2003 IEEE Bologna
Print_ISBN
0-7803-7967-5
Type
conf
DOI
10.1109/PTC.2003.1304325
Filename
1304325
Link To Document