DocumentCode
422799
Title
Three phase harmonic load flow in an unbalanced AC system including HVDC link
Author
Hosseini, S.H. ; Sajadi, A. ; Teimouri, M.
Author_Institution
Azarbyjan Regional Electr. Co., Tabriz, Iran
Volume
3
fYear
2004
fDate
14-16 Aug. 2004
Firstpage
1726
Abstract
Recent technology advances have made HVDC transmission an economically attractive alternative for power transmission over long distances. In unbalanced conditions ,the AC to DC and DC to AC conversion processes in the HVDC transmission ,in addition to characteristic harmonics generate non characteristic harmonics. When calculating non characteristic harmonics generated by HVDC converters, because of unbalance at the AC system ,three phase HVAC/HVDC load flow must be taken in solution. In this paper therefore, equations of three phase HVAC/HVDC load flow is explored. Finally, three phase harmonic load flow was done by three phase frequency scan technique in an unbalanced AC system including HVDC link.
Keywords
AC-DC power convertors; DC-AC power convertors; HVDC power convertors; HVDC power transmission; harmonic distortion; load flow; power conversion harmonics; power supply quality; AC-DC conversion process; DC-AC conversion process; HVAC load flow; HVDC converter; HVDC power transmission; harmonic distortion; three phase frequency scan technique; three phase harmonics; unbalanced AC system;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Motion Control Conference, 2004. IPEMC 2004. The 4th International
Conference_Location
Xi´an
Print_ISBN
7-5605-1869-9
Type
conf
Filename
1377009