Unbalance in Parallel Interconnector Circuits
Author
Evans, J.C.
Author_Institution
Mott MacDonald Ltd., Newcastle upon Tyne
Volume
1
fYear
2006
fDate
6-8 Sept. 2006
Firstpage
328
Lastpage
332
Abstract
This paper investigates current unbalance in parallel cable interconnector circuits. Several instances have been observed where an MV switchboard loses supply during a motor starting transient. In each instance the affected switchboard was supplied via two interconnector cables operating in parallel. During motor starting, the transient current was not shared equally between the interconnector red, blue and yellow phases. The protection on each interconnector interpreted the unbalance in the phases as an earth fault and initiated a trip. To establish that the unbalance is not due to load or current transformer spill current, steady-state and transient measurements have been made. Steady-state and transient PSCAD simulations have been performed to investigate possible causes of the unequal current sharing between parallel interconnectors.
Keywords
electric machines; interconnections; machine protection; power cables; starting; MV switchboard loses supply; PSCAD simulations; current transformer; earth fault; load transformer; motor starting transient; parallel cable interconnector circuits; steady-state measurements; transient current; transient measurements; Circuit faults; Current measurement; Current transformers; Earth; Integrated circuit interconnections; PSCAD; Power system transients; Protection; Sea measurements; Steady-state;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference, 2006. UPEC '06. Proceedings of the 41st International
Conference_Location
Newcastle-upon-Tyne
Print_ISBN
978-186135-342-9
Type
conf
DOI
10.1109/UPEC.2006.367769
Filename
4218698
Link To Document