DocumentCode
468454
Title
Potential distribution analysis and improvement of 1000 kV gas insulted switch metal oxide arrester
Author
Meng, Bowen ; Zhang, Bo ; He, Jinliang
Author_Institution
Tsinghua Univ., Beijing
fYear
2007
fDate
8-11 Oct. 2007
Firstpage
1321
Lastpage
1326
Abstract
This paper presents the study on the potential distribution of the 1000 kV gas insulated switch (GIS) metal oxide arrester (MOA). Based on the idea of field-circuit combination, the 3D finite element method (FEM) and circuit analytic method are applied to analyze and improve the potential distribution of the 1000 kV MOA. The methods of adjusting the grading rings, increasing the voltage level of the ZnO discs and adding parallel capacitors are analyzed to improve the potential distribution of the GIS MOA. Regulations of the three methods are studied and optimal schemes of the GIS MOA are achieved to improve the potential distribution coefficient to be within +15%.
Keywords
arresters; finite element analysis; gas insulated switchgear; power capacitors; 3D finite element method; FEM; circuit analytic method; field-circuit combination; gas insulted switch metal oxide arrester; parallel capacitors; potential distribution analysis; voltage 1000 kV; Arresters; Capacitors; Circuit analysis; Finite element methods; Gas insulation; Geographic Information Systems; Switches; Switchgear; Voltage; Zinc oxide;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Machines and Systems, 2007. ICEMS. International Conference on
Conference_Location
Seoul
Print_ISBN
978-89-86510-07-2
Electronic_ISBN
978-89-86510-07-2
Type
conf
Filename
4411945