• DocumentCode
    490899
  • Title

    Monitoring of Battery Operation Data in UPS Systems

  • Author

    Boettger, Klaus

  • Author_Institution
    AEG Aktiengesellschaft, Elisabethenstr. 29, D-6100 Darmstadt
  • fYear
    1985
  • fDate
    14-17 Oct. 1985
  • Firstpage
    605
  • Lastpage
    610
  • Abstract
    Storage batteries for computer feeding UPS systems are, in german engineering practice, predominantly rated for a shorttime performance lasting some 7-10 minutes. Given this high rate loading, we experience considerable variations in battery output coefficient with any load demand changes. UPS installations as a whole should therefore offer, under part load, a much prolonged bridging-over period than when supplying their nominal load. It is not however easy to assess such additional reserves in power, particularly not after a partial discharge. Hence the destinct expectation, on the part of UPS operators, of a reliable registration mode, i.e. by annunciator for the prevailing battery potential remaining to them in each case. The present paper outlines suitable designs for a battery status monitor, and the application of such a condition annunciator to diverse UPS configurations.
  • Keywords
    Battery charge measurement; Computerized monitoring; Condition monitoring; Current measurement; Data engineering; Displays; Inverters; Power measurement; Uninterruptible power systems; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1985. INTELEC '85. Seventh International
  • Conference_Location
    Munich, Federal Republic of Germany
  • Print_ISBN
    3-8007-1429-9
  • Type

    conf

  • Filename
    4794293