DocumentCode
49925
Title
Detecting synchrophasors computed over fault/switching transients
Author
Das, S. ; Sidhu, Tarlochan
Author_Institution
Electr. & Comput. Eng., Univ. of Western Ontario, London, ON, Canada
Volume
8
Issue
9
fYear
2014
fDate
Sept. 2014
Firstpage
1616
Lastpage
1625
Abstract
Faults and switching operations often cause step changes in voltage and current waveforms. A fault/switching transient synchrophasor is computed over a window of pre- and post-fault/switching samples. Many synchrophasor applications are not designed to use these transient synchrophasors. So, there is a need to detect fault/switching transient synchrophasors. A robust algorithm is proposed to detect synchrophasors computed over switching/fault transients. The proposed algorithm runs in phasor measurement unit. The proposed algorithm performs satisfactorily in the presence of noises, harmonics, off nominal frequencies, decaying DC and missing/bad samples. The proposed algorithm can detect fault/switching transient synchrophasors caused by smaller or larger disturbances. The proposed algorithm is simple, non-iterative and mainly needs additions. Possible applications of the proposed algorithm are also discussed.
Keywords
phasor measurement; current waveform; fault-switching transient synchrophasor; robust algorithm; synchrophasors detection; voltage waveform;
fLanguage
English
Journal_Title
Generation, Transmission & Distribution, IET
Publisher
iet
ISSN
1751-8687
Type
jour
DOI
10.1049/iet-gtd.2013.0493
Filename
6887476
Link To Document