• DocumentCode
    501976
  • Title

    A new method to eliminate DG´s negative effects on the existing distribution network protection

  • Author

    Wang, Hui

  • Author_Institution
    Shanghai Municipal Electric Power Company of State Grid - China
  • fYear
    2009
  • fDate
    8-11 June 2009
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Distributed Generation (DG) will affect the amperage, direction and distribution of fault current. With the penetration of DG, the existing protection and automatic devices may not operate correctly. In accordance with how DG affects the protection of distribution system, the importance of connecting a fault current limiter (FCL) to DG to restrict the fault current is analyzed, and the detailed algorithm to get the parameters of FCL is presented with a case. In the end, through the simulation by Matlab/EMTP we proved that FCL with properly selected parameters can effectively restrict DG´s fault current, eliminate DG´s negative effects and guarantee the original protection´s reliability and selectivity. In addition, We can also add direction protection to solve the problem of DG´s backward fault current if necessary.
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
  • Conference_Location
    Prague, Czech Republic
  • ISSN
    0537-9989
  • Print_ISBN
    978-1-84919126-5
  • Type

    conf

  • Filename
    5255307