• DocumentCode
    509648
  • Title

    Confirming the reliability and safety of MV distribution network including DG applying protection applications for earth faults

  • Author

    Nikander, A.

  • fYear
    2009
  • fDate
    8-11 June 2009
  • Firstpage
    1
  • Lastpage
    1
  • Abstract
    The paper describes the effects of distributed generation on the earth fault protection of a medium voltage feeder and protection coordination. Neutral isolated and compensated systems were considered. The aim was to investigate the behaviour of the production unit during automatic reclosings, especially as regards electrical safety. Methods possibly feasible for clearing a temporary earth fault without voltage break were considered. Thus disturbances affecting production and customers are less than with automatic reclosings. The method of the study was dynamic simulation of the earth faults in medium voltage system. The network model including a wind power plant was implemented applying PSCADtrade simulation software.
  • Keywords
    distributed power generation; earthing; electrical safety; fault diagnosis; power distribution protection; power distribution reliability; DG applying protection applications; MV distribution network reliability; MV distribution network safety; PSCAD simulation software; compensated systems; earth faults; electrical safety; medium voltage feeder; neutral isolated systems; protection coordination; wind power plant;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution - Part 2, 2009. CIRED 2009. The 20th International Conference and Exhibition on
  • Conference_Location
    Prague
  • Print_ISBN
    978-1-84919-160-9
  • Type

    conf

  • Filename
    5371199