    Localization of short-circuits on a medium voltage feeder with distributed generation

  • Author

    Marvik, J.I. ; Hoidalen, H.K. ; Petterteig, A.

  • Author_Institution
    NTNU, Trondheim, Norway
  • fYear
    2009
  • fDate
    8-11 June 2009
  • Firstpage
    1
  • Lastpage
    1
  • Abstract
    The paper deals with localization of phase-to-phase short-circuits on a medium voltage (MV) feeder with distributed generation (DG). Fundamental frequency currents and voltages are utilized for estimating the distance to the fault location. Loads and DG connected to the feeder cause errors in the estimated distance. Two methods to compensate for these errors are presented in the paper. In compensation method A, pre-fault measurements from the DG-unit are utilized for estimating the DG-current during fault. In compensation method B, the magnitude of the DG-current and-voltage during fault is measured. A method for utilizing the DG-node measurements to discriminate between faults on the main and on a lateral branch is also presented. The goal is to obtain sufficiently accurate fault localization with limited information from the feeder available.
  • Keywords
    distributed power generation; fault location; short-circuit currents; DG-node measurement; distance estimation; distributed generation; fault localization; fault location; fundamental frequency current; medium voltage feeder; phase-to-phase short-circuit; prefault measurement; short-circuit localization;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution - Part 2, 2009. CIRED 2009. The 20th International Conference and Exhibition on
  • Conference_Location
    Prague
  • Print_ISBN
    978-1-84919-160-9
  • Type

    conf

  • Filename
    5371250