• DocumentCode
    509758
  • Title

    Changes in insulation condition of dry cured XLPE cables over a 6-year period

  • Author

    Jorgensen, H.J.

  • Author_Institution
    Danish Energy Assoc., Denmark
  • fYear
    2009
  • fDate
    8-11 June 2009
  • Firstpage
    1
  • Lastpage
    1
  • Abstract
    The service experience with dry cured XLPE cables is good and their internal failure rate is much lower than is the case for the older steam cured cables. However, water tree aging also occurs in dry cured cables, unless the insulation is protected against moisture by water barriers. Since 2001, a series of diagnostic measurements has been carried out on in total 58 dry cured XLPE cable sections without water barrier. The cables were installed in 10 kV to 20 kV networks in the period between 1979 and 1996. The objective of these measurements has been to get an assessment of the insulation condition and the rate of change in insulation condition for these cable sections and the results are presented in the paper.
  • Keywords
    XLPE insulation; fault diagnosis; power cable insulation; diagnostic measurements; dry cured XLPE cables; insulation condition; internal failure rate; steam cured cables; voltage 10 kV to 20 kV; water barriers; water tree aging;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution - Part 2, 2009. CIRED 2009. The 20th International Conference and Exhibition on
  • Conference_Location
    Prague
  • Print_ISBN
    978-1-84919-160-9
  • Type

    conf

  • Filename
    5371315