DocumentCode :
510995
Title :
Estimation of 80kA short-line fault interrupting capability in an SF6 gas circuit breaker based on arc model calculation
Author :
Urai, H. ; Ooshita, Y. ; Koizumi, M. ; Yaginuma, N. ; Tsukushi, M. ; Smeets, R.P.P.
fYear :
2008
fDate :
7-12 Sept. 2008
Firstpage :
129
Lastpage :
132
Abstract :
Interrupting performances of high-voltage circuit breakers have been quantitatively evaluated through current zero measurements during interrupting tests. The interrupting capability of circuit breakers can also be estimated by means of an arc model calculation, the parameters of which are determined through current zero measurement. An actual case where the arc model calculation was used for the development of an 80kA circuit breaker is discussed in this paper. We estimated the 80kA interrupting capability based on the current zero data measured during 50kA interrupting tests, which had already been carried out with a similar type of circuit breaker. We designed the necessary capacitance for short-line fault interruption by means of the arc model calculation. The test results agreed well with the predicted performance.
Keywords :
SF6 insulation; circuit breakers; circuit-breaking arcs; short-circuit currents; SF6 gas circuit breaker; apparent power 80 kVA; arc model calculation; current 80 kA; current zero measurement; high-voltage circuit breakers; short-line fault interruption; Capacitance; Circuit breakers; Circuit faults; Circuit testing; Current measurement; Laboratories; Power system modeling; Sulfur hexafluoride; System testing; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Gas Discharges and Their Applications, 2008. GD 2008. 17th International Conference on
Conference_Location :
Cardiff
Print_ISBN :
978-0-9558052-0-2
Type :
conf
Filename :
5379310
Link To Document :
بازگشت