DocumentCode
535691
Title
Measured impedance at relaying point for faults on line behind
Author
Shateri, H. ; Jamali, S.
Author_Institution
Centre of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran, Iran
fYear
2010
fDate
Aug. 31 2010-Sept. 3 2010
Firstpage
1
Lastpage
5
Abstract
Distance relays are one of the mostly used protective devices in transmission systems. These relays are used as main, first zone and a part of second zone, and backup, the rest of second zone and third zone, protective devices. Fault resistance is a source of error for distance relays in the form of the measured impedance deviation from its actual value. This paper investigates the measured impedance by distance relays for the faults on the line behind by means of presenting the measured impedance at the relaying point and distance relay ideal tripping characteristic. The variation of ideal tripping characteristic duo the changes in the power system parameters is investigated.
Keywords
electric impedance measurement; power transmission faults; power transmission lines; relays; distance relays; fault resistance; impedance measurement; line faults; power system parameter; relaying point; transmission systems; Circuit faults; Electrical resistance measurement; Impedance; Impedance measurement; Power systems; Protective relaying; Resistance; Distance relay; Fault resistance; Measured impedance; Third protective zone;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference (UPEC), 2010 45th International
Conference_Location
Cardiff, Wales
Print_ISBN
978-1-4244-7667-1
Type
conf
Filename
5649898
Link To Document