DocumentCode :
535691
Title :
Measured impedance at relaying point for faults on line behind
Author :
Shateri, H. ; Jamali, S.
Author_Institution :
Centre of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran, Iran
fYear :
2010
fDate :
Aug. 31 2010-Sept. 3 2010
Firstpage :
1
Lastpage :
5
Abstract :
Distance relays are one of the mostly used protective devices in transmission systems. These relays are used as main, first zone and a part of second zone, and backup, the rest of second zone and third zone, protective devices. Fault resistance is a source of error for distance relays in the form of the measured impedance deviation from its actual value. This paper investigates the measured impedance by distance relays for the faults on the line behind by means of presenting the measured impedance at the relaying point and distance relay ideal tripping characteristic. The variation of ideal tripping characteristic duo the changes in the power system parameters is investigated.
Keywords :
electric impedance measurement; power transmission faults; power transmission lines; relays; distance relays; fault resistance; impedance measurement; line faults; power system parameter; relaying point; transmission systems; Circuit faults; Electrical resistance measurement; Impedance; Impedance measurement; Power systems; Protective relaying; Resistance; Distance relay; Fault resistance; Measured impedance; Third protective zone;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference (UPEC), 2010 45th International
Conference_Location :
Cardiff, Wales
Print_ISBN :
978-1-4244-7667-1
Type :
conf
Filename :
5649898
Link To Document :
بازگشت