DocumentCode :
538992
Title :
Impacts of HVAC interconnection parameters on inter-area ocsillation
Author :
Nguyen, Mai H. ; Saha, Tapan K. ; Eghbal, Mehdi
Author_Institution :
Sch. of Inf. Technol. & Electr. Eng., Univ. of Queensland, Brisbane, QLD, Australia
fYear :
2010
fDate :
5-8 Dec. 2010
Firstpage :
1
Lastpage :
6
Abstract :
This paper investigates the impacts of distance and power flow of transmission line interconnections on the inter-area oscillations. The effectiveness of Power System Stabiliser (PSS) in damping the inter-area oscillations is studied considering various combinations of interconnection power flows and distances. Simulations are carried out on a two area 4 generator test system as well as on the simplified South East Australian power system. Time domain simulations are also used to explain the behaviour of the system subjected to a small disturbance. Simulation results show that the inter-area mode is less stable when the length of the interconnection increases. However, with the presence of PSS, satisfactory performance is observed. It is also shown that power flow of the interconnection does not have a considerable impact on the damping ratio.
Keywords :
HVAC; load flow; oscillations; power system interconnection; power system stability; power transmission lines; time-domain analysis; HVAC interconnection parameters; PSS; South East Australian power system; generator test system; inter-area oscillation damping; power flow; power system stabiliser; time domain simulations; transmission line interconnections; Damping; Eigenvalues and eigenfunctions; Generators; Oscillators; Power system dynamics; Power system stability; Interarea oscillation; damping; interconnection; small signal stability;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference (AUPEC), 2010 20th Australasian
Conference_Location :
Christchurch
Print_ISBN :
978-1-4244-8379-2
Electronic_ISBN :
978-1-4244-8380-8
Type :
conf
Filename :
5710748
Link To Document :
بازگشت