• DocumentCode
    548045
  • Title

    Investigating the impact of static load models on islanding detection

  • Author

    Mahboobynejad, Amir ; Golshan, Mohamad Esmail Hamedani ; Hadadzadeh, Abolfazl

  • Author_Institution
    Isfahan University of Technology
  • fYear
    2011
  • fDate
    17-19 May 2011
  • Firstpage
    1
  • Lastpage
    1
  • Abstract
    Summary from only given. Usually in Distributed Generation islanding detection studies, constant RLC loads were supposed as the hardestdetectable case. Therefore, anti-islanding methods evaluated by using this type of the load. In this paper the performance of two passive methods (over/under voltage and over/under frequency protection or OVP/UVP and OFP/UFP) is tested for the loads that have voltage and frequency dependence. several loading conditions with different parameters of the load is considered and the results are compared with constant RLC load case. The constant power-controlled interface control of inverter-based DG is designed to operate at unity power factor. The Nondetection zone for these methods is derived analytically in terms of the load´s parameters.
  • Keywords
    Inverter-based Distributed-Generation; OVP/UVP and OFP/UFP; islanding; load model;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering (ICEE), 2011 19th Iranian Conference on
  • Conference_Location
    Tehran
  • Print_ISBN
    978-1-4577-0730-8
  • Type

    conf

  • Filename
    5955935