DocumentCode
548045
Title
Investigating the impact of static load models on islanding detection
Author
Mahboobynejad, Amir ; Golshan, Mohamad Esmail Hamedani ; Hadadzadeh, Abolfazl
Author_Institution
Isfahan University of Technology
fYear
2011
fDate
17-19 May 2011
Firstpage
1
Lastpage
1
Abstract
Summary from only given. Usually in Distributed Generation islanding detection studies, constant RLC loads were supposed as the hardestdetectable case. Therefore, anti-islanding methods evaluated by using this type of the load. In this paper the performance of two passive methods (over/under voltage and over/under frequency protection or OVP/UVP and OFP/UFP) is tested for the loads that have voltage and frequency dependence. several loading conditions with different parameters of the load is considered and the results are compared with constant RLC load case. The constant power-controlled interface control of inverter-based DG is designed to operate at unity power factor. The Nondetection zone for these methods is derived analytically in terms of the load´s parameters.
Keywords
Inverter-based Distributed-Generation; OVP/UVP and OFP/UFP; islanding; load model;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Engineering (ICEE), 2011 19th Iranian Conference on
Conference_Location
Tehran
Print_ISBN
978-1-4577-0730-8
Type
conf
Filename
5955935