DocumentCode :
560683
Title :
The temperature dependence of insulation characteristics of transformer oil at low temperatures
Author :
Gao, Ming ; Li, Guangfan ; Li, Jinzhong ; Zhao, Zhigang
Author_Institution :
China Electr. Power Res. Inst., Beijing, China
Volume :
2
fYear :
2011
fDate :
8-9 Sept. 2011
Firstpage :
27
Lastpage :
30
Abstract :
This paper presents the test methods of studying insulation characteristics of transformer oil at low temperatures. Karamay DB-45 transformer oils were selected as the initial specimens. Oil samples of different quality indexes were obtained after processing by the vacuum oil purifier. Each kind of oil sample was carried out experiments on insulating properties at low temperatures. The temperature dependence of the dielectric strength of transformer oil at low temperatures (-20°C~10°C) is obtained by statistical analysis of test results. (1)The relation curves of breakdown voltage vs. temperature show “U”-type features when the water content is high. (2)Water content is the main influence factor of breakdown voltage of transformer oils. (3)In general, the values of the transformer oil breakdown voltage measured at room temperature do not represent their breakdown voltage level at low temperatures. (4)If the oil samples meet the requirements of the current EHV/UHV transformer oil standards, the impact of temperature on the breakdown voltage is very small at low temperatures. (5)The permittivity and the dielectric loss factor of transformer oils little change in the range of -20°C~10°C.
Keywords :
electric breakdown; electric strength; power transformer insulation; transformer oil; Karamay DB-45 transformer oil; breakdown voltage relation curve; current EHV-UHV transformer oil standard; dielectric loss factor; dielectric strength; insulation characteristic; permittivity loss factor; statistical analysis; temperature -20 degC to 10 degC; temperature 293 K to 298 K; temperature dependence; vacuum oil purifier; water content; Oil insulation; Oils; Power transformer insulation; Temperature; Temperature measurement; Water pollution; insulation characteristics; low temperature; transformer oil;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering and Automation Conference (PEAM), 2011 IEEE
Conference_Location :
Wuhan
Print_ISBN :
978-1-4244-9691-4
Type :
conf
DOI :
10.1109/PEAM.2011.6134900
Filename :
6134900