• DocumentCode
    56374
  • Title

    Reclaiming aged transformer oil with activated bentonite and enhancing reclaimed and fresh transformer oils with antioxidants

  • Author

    Raymon, A. ; Karthik, R.

  • Author_Institution
    Dept. of EEE, Renganayagi Varatharaj Coll. of Eng., Salvarpatti, India
  • Volume
    22
  • Issue
    1
  • fYear
    2015
  • fDate
    Feb. 2015
  • Firstpage
    548
  • Lastpage
    555
  • Abstract
    Transformers are the vital units of power system and the major dielectric used in transformer is petroleum based mineral oil, which acts both as an insulating medium and potential coolant. This work focuses on reclaiming aged mineral oil using activated bentonite and enhancing the critical characteristics of reclaimed mineral oil and fresh transformer oil using antioxidants. The reclamation is carried by treating 500 ml aged mineral oil with 5 g activated bentonite quantity. Then the treated sample is mixed with different combinations of natural and synthetic antioxidants. The enhancement of fresh transformer oil is carried by adding multiple combinations of antioxidants with different mechanisms like free radical scavenging, metal chelating and synergism. The critical parameters like breakdown voltage, viscosity, flash point and fire point of the samples are calculated using ASTM and IEC specifications before and after adding antioxidants. The recorded parameters prove that the reclaimed aged mineral oil after added with high performance antioxidant combinations can perform superior than base fluids and can be reused in power transformers. Moreover the enhanced fresh transformer oil with antioxidants shows greater improvement and this technique could be possibly employed for reclamation (regenerating) and enhancement of waste insulating oils.
  • Keywords
    coolants; power transformers; transformer oil; activated bentonite; aged mineral oil; aged transformer oil; antioxidants; breakdown voltage; fire point; flash point; free radical scavenging; fresh transformer oil; insulating medium; metal chelating; potential coolant; power system; reclaimed mineral oil; synergism; viscosity; waste insulating oils; Aging; Fluids; Minerals; Oil insulation; Power transformer insulation; Temperature measurement; Power transformer; antioxidants; critical parameters; dielectric; transformer oil;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.004094
  • Filename