• DocumentCode
    565848
  • Title

    Research of the dead-time compensation based on the three-phase grid-connected inverter

  • Author

    Liu, Yan ; Ben, Hongqi ; Li, Chunpeng ; Wang, Daqing

  • Author_Institution
    School of Electrical Engineering and Automation, Harbin Institute of Technology, China
  • Volume
    1
  • fYear
    2012
  • fDate
    2-5 June 2012
  • Firstpage
    510
  • Lastpage
    514
  • Abstract
    Time delay must be inserted in the switching signals to prevent the simultaneous conduction of two switching devices in the same leg of the inverter, however, this results in a decrease of the fundamental component and an increase of the odd-order except the triple-n harmonics of the output voltage of the inverter. The distortion of output voltage further distorts the output current in turn. This paper analyses the dead-time effect in detail under Space Vector Pulse Width Modulation (SVPWM), and presents a general computation method of the harmonics of the error voltage. On this basis, a dead-time compensation scheme is proposed. MATLAB simulations and experiments are carried out based on the three-phase grid-connected inverter. The results well demonstrate the effectiveness of the proposed strategy and proved that this system has the advantage of high power factor in the AC side and little harmonics pollution to the grid.
  • Keywords
    Harmonic analysis; Inverters; Power harmonic filters; Space vector pulse width modulation; Switches; dead time compensation; dead time effect; three-phase grid-connected inverter;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics and Motion Control Conference (IPEMC), 2012 7th International
  • Conference_Location
    Harbin, China
  • Print_ISBN
    978-1-4577-2085-7
  • Type

    conf

  • DOI
    10.1109/IPEMC.2012.6258787
  • Filename
    6258787