• DocumentCode
    57308
  • Title

    An Innovative Pilot Relaying Scheme for Shunt-Compensated Line

  • Author

    Gupta, Om Hari ; Tripathy, Manoj

  • Author_Institution
    Dept. of Electr. Eng., Indian Inst. of Technol. Roorkee, Roorkee, India
  • Volume
    30
  • Issue
    3
  • fYear
    2015
  • fDate
    Jun-15
  • Firstpage
    1439
  • Lastpage
    1448
  • Abstract
    This paper presents a fault detection and classification scheme for a shunt [static var compensator (SVC)] compensated line. The proposed relaying scheme is based on the concept of superimposed sequence components-based integrated impedance (SSCII). For an internal fault, the magnitude of SSCII is small and for an external fault, it is very large. In the SVC compensated line, a fault forces SVC to vary its impedance. Superimposed components are injected due to this impedance variation, along with the fault components. These SVC-injected components are treated as fault-injected components and, therefore, even the sound phases are detected as faulty phases. To avoid such failure, fault-injected superimposed components have been extracted by using the modified prefault data, which is estimated according to SVC impedance variations. The superimposed components measured using the modified prefault data consist of fault-injected superimposed components only. The proposed scheme has been tested for all types of faults, different values of fault resistances, and several fault locations and SVC locations. The results demonstrate that the proposed scheme successfully detects and classifies the faults. Also, the proposed scheme is robust against variations in fault resistance, source impedance, and SVC location.
  • Keywords
    fault location; power system relaying; power transmission faults; power transmission reliability; static VAr compensators; SSCII; SVC; fault classification scheme; fault detection scheme; fault locations; fault resistances; fault-injected superimposed components; internal fault; pilot relaying scheme; shunt-compensated line; static var compensator; superimposed sequence components-based integrated impedance; Circuit faults; Communication channels; Impedance; Relays; Resistance; Static VAr compensators; Voltage measurement; Fault classification; integrated impedance; pilot relaying; protection of compensated line; static var compensator (SVC);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2015.2394353
  • Filename
    7035054