DocumentCode :
57519
Title :
Transformer Voltage Regulation—Compact Expression Dependent on Tap Position and Primary/Secondary Voltage
Author :
Todorovski, Mile
Author_Institution :
Fac. of Electr. Eng. & Inf. Technol., Univ. Ss. Cyril & Methodius, Skopje, Macedonia
Volume :
29
Issue :
3
fYear :
2014
fDate :
Jun-14
Firstpage :
1516
Lastpage :
1517
Abstract :
This letter presents a compact transformer voltage regulation expression which accounts for off-nominal tap position and voltage deviation from the nominal value. The expression is validated through comparison with the common expressions used in the literature. It is shown that the primary/secondary voltage variation has a certain influence on the results which were not taken into account in previous compact forms of the voltage regulation expression.
Keywords :
power transformers; voltage control; compact transformer voltage regulation; off-nominal tap position; primary voltage variation; secondary voltage variation; voltage deviation; Admittance; Equivalent circuits; Impedance; Mathematical model; Power systems; Voltage control; Voltage measurement; Off-nominal turns ratio; short-circuit voltage; transformer; transformer impedance; voltage regulation;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2014.2311959