• DocumentCode
    586779
  • Title

    Implementation of Dynamic Transformer Rating in a distribution network

  • Author

    Jalal, Thahirah Syed ; Rashid, N. ; van Vliet, B.

  • Author_Institution
    Unison Networks Ltd., New Zealand
  • fYear
    2012
  • fDate
    Oct. 30 2012-Nov. 2 2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Unison Networks Limited is currently implementing Dynamic Transformer Rating (DTR) on most of the power transformers in its distribution network. The implementation involves 50 transformers across three different regions - Hawkes Bay, Taupo and Rotorua. The DTR scheme utilizes an in-house developed DTR algorithm that has been designed based on the IEC60076-7 Loading Guide for Oil Immersed Power Transformer Standard. The algorithm samples real time data from various sensors installed in the networks and translates them into dynamic rating and insulation loss of life information for each transformer.
  • Keywords
    distribution networks; power transformers; transformer oil; DTR algorithm; IEC60076-7 loading guide; dynamic transformer rating; insulation loss; oil immersed power transformer standard; realtime data; Algorithm design and analysis; Insulation; Load modeling; Loading; Materials; Thermal loading; Power transformers; distribution networks; smart grids;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology (POWERCON), 2012 IEEE International Conference on
  • Conference_Location
    Auckland
  • Print_ISBN
    978-1-4673-2868-5
  • Type

    conf

  • DOI
    10.1109/PowerCon.2012.6401328
  • Filename
    6401328