DocumentCode
586779
Title
Implementation of Dynamic Transformer Rating in a distribution network
Author
Jalal, Thahirah Syed ; Rashid, N. ; van Vliet, B.
Author_Institution
Unison Networks Ltd., New Zealand
fYear
2012
fDate
Oct. 30 2012-Nov. 2 2012
Firstpage
1
Lastpage
5
Abstract
Unison Networks Limited is currently implementing Dynamic Transformer Rating (DTR) on most of the power transformers in its distribution network. The implementation involves 50 transformers across three different regions - Hawkes Bay, Taupo and Rotorua. The DTR scheme utilizes an in-house developed DTR algorithm that has been designed based on the IEC60076-7 Loading Guide for Oil Immersed Power Transformer Standard. The algorithm samples real time data from various sensors installed in the networks and translates them into dynamic rating and insulation loss of life information for each transformer.
Keywords
distribution networks; power transformers; transformer oil; DTR algorithm; IEC60076-7 loading guide; dynamic transformer rating; insulation loss; oil immersed power transformer standard; realtime data; Algorithm design and analysis; Insulation; Load modeling; Loading; Materials; Thermal loading; Power transformers; distribution networks; smart grids;