DocumentCode
613405
Title
Comparison of different approaches to arc fault location on power transmission lines
Author
Pustulka, M. ; Izykowski, J. ; Lukowicz, M.
Author_Institution
Inst. of Electr. Power Eng., Wroclaw Univ. of Technol., Wroclaw, Poland
fYear
2013
fDate
5-8 May 2013
Firstpage
145
Lastpage
149
Abstract
This paper presents a three different fault location approaches: one-end Takagi algorithm, two-end algorithm considering natural fault loops and neural network. It is assumed that three-phase voltages and currents from both ends of the line measured asynchronously are the input signals of the fault locator. In addition to natural fault loop signals also use of symmetrical components (positive and negative or incremental positive sequence components) to fault location were considered as well. Results of evaluation study have been included, analyzed and discussed. Influence of filtration have been also considered.
Keywords
arcs (electric); fault location; power filters; power transmission lines; Takagi algorithm; arc fault location; filtration; incremental positive sequence components; natural fault loop signals; neural network; power transmission lines; symmetrical components; Current measurement; Fault location; Impedance; Mathematical model; Neural networks; Synchronization; Voltage measurement; arc fault; location; neural network; signal processing;
fLanguage
English
Publisher
ieee
Conference_Titel
Environment and Electrical Engineering (EEEIC), 2013 12th International Conference on
Conference_Location
Wroclaw
Print_ISBN
978-1-4673-3060-2
Type
conf
DOI
10.1109/EEEIC.2013.6549606
Filename
6549606
Link To Document