• DocumentCode
    615598
  • Title

    The influence of corona near to the bushing of a transformer on partial discharge measurement with an acoustic emission sensor

  • Author

    Najafi, Seyed Amir Mahmood ; Peimankar, Abdolrahman ; Saadati, Hassan ; Gockenbach, E. ; Borsi, H.

  • Author_Institution
    Inst. of Electr. Power Syst., Leibniz Univ. Hannover, Hannover, Germany
  • fYear
    2013
  • fDate
    2-5 June 2013
  • Firstpage
    295
  • Lastpage
    298
  • Abstract
    Partial discharge (PD) detection is one of the most important issues in order to determine the insulation condition of power transformers; however the procedures for electrical partial discharge detecting are sometimes not so beneficial for onsite and on-line measurements due to excessive interferences. Acoustic emission (AE) PD detecting method may have some advantages in comparing electrical as well as optical and chemical methods. With this method it is possible to identify the type of PD from the collected information and with a set of sensors to locate the PD source and to evaluate the severity of PD activity. Using multiple sensors, the time delay between the sensors can be used in order to locate the PD source within the power transformer. Protection against electromagnetic interference (EMI) is another advantage of the acoustic method over the electrical method. However the acoustic emission signal from e.g. corona on a transformer bushing could cause some influence on acoustic emission signals due to the short distance between acoustic source and sensor. In this paper, the effect of this kind of acoustic noise has been measured with two different types of acoustic sensors (75 kHz and 150 kHz) at different PD activities and amount of apparent charges, in order to compare the sensitivity of the two sensors on the acoustic noise superimposed on the PD signal. The results are that the two sensors show different sensitivity and the sensor with the maximum frequency resonant at 150 kHz is more reliable for acoustic signals of PD inside the power transformer.
  • Keywords
    acoustic emission testing; acoustic noise; corona; electromagnetic interference; partial discharge measurement; power transformer insulation; power transformer testing; EMI; acoustic emission sensor; acoustic noise; corona; electromagnetic interference; frequency 150 kHz; frequency 75 kHz; insulation condition; partial discharge detection; partial discharge measurement; power transformers; time delay; transformer bushing; Acoustic measurements; Acoustics; Corona; Insulators; Partial discharges; Power transformer insulation; AE; Acoustic Emission Signal; Bushing; Corona; PD;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference (EIC), 2013 IEEE
  • Conference_Location
    Ottawa, ON
  • Print_ISBN
    978-1-4673-4738-9
  • Electronic_ISBN
    978-1-4673-4739-6
  • Type

    conf

  • DOI
    10.1109/EIC.2013.6554253
  • Filename
    6554253