DocumentCode
618794
Title
Design and construction of a prototype saline solution resistive voltage divider
Author
Phoaphan, Busayapol ; Potivejkul, S. ; Chaisiri, Prach ; Yutthagowith, Peerawut
Author_Institution
Electr. Eng. Dept., King Mongkut´s Inst. of Technol. Ladkrabang, Bangkok, Thailand
fYear
2013
fDate
15-17 May 2013
Firstpage
1
Lastpage
4
Abstract
This paper presents design and construction of a prototype resistive voltage measuring system composing of a saline solution divider and resistive attenuator. The structure of the developed divider is designed in form of coaxial cylinder. The system has voltage rating of 300 kV. The developed measuring system has been test according to the IEC standard composing of unit step response test, scale factor test, withstand voltage test, and short term stability test. The experimental response times of the developed voltage measuring systems without and with shielding ring are about 50 ns and 25 ns, respectively. This accomplishment will be advantage for increasing capability of HV laboratory and for researches, which are about effect of fast transient voltage in transmission and distribution systems in Thailand.
Keywords
voltage dividers; voltage measurement; IEC standard; coaxial cylinder; fast transient voltage; prototype resistive voltage measuring system; resistive attenuator; saline solution divider; scale factor test; short term stability test; unit step response test; voltage 300 kV; withstand voltage test; Attenuators; Capacitance; Lightning; Linearity; Resistors; Time factors; Voltage measurement; Fast transient; Lightning impulse voltage; Resistive voltage divider; Saline solution; Step response;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2013 10th International Conference on
Conference_Location
Krabi
Print_ISBN
978-1-4799-0546-1
Type
conf
DOI
10.1109/ECTICon.2013.6559580
Filename
6559580
Link To Document