Characteristics of the voltage and current in singlephase faults on reactored transmission lines
Author :
Shao Wenquan ; Zhang Xiaowei ; Song Jiangxi ; Nan Shugong
Author_Institution :
Dept. of Electron. & Inf., Xi´an Polytech. Univ., Xi´an, China
fYear :
2012
fDate :
18-20 Sept. 2012
Firstpage :
1
Lastpage :
4
Abstract :
Because of using a fixed-time, present single-phase reclosure techniques on transmission lines have poor ability of detecting non-fault before reclosing. It is necessary to detect non-fault to avoid unsuccessful reclosing in arcing faults or permanent faults. Then it is essential to improve the effectiveness of the non-fault detection based on reliable data. Therefore, this paper discussed the amplitudes of the terminal-voltage and the current in the shunt reactor under different fault conditions in single-phase arcing faults and non-arc faults respectively. The results show that the current is more reliable than the voltage in most arcing faults and non-arc faults, so it is feasible to employ comprehensive criterion using voltage and current for increasing the accuracy of the non-fault detection.
Keywords :
arcs (electric); fault location; power transmission faults; reactors (electric); current amplitudes; fault conditions; nonarc faults; nonfault detection; reactored transmission lines; shunt reactor; single-phase arcing faults; terminal-voltage amplitudes; Circuit faults; Fault location; Inductors; Power transmission lines; Resistance; Shunts (electrical); non-fault detection; shunt reactors; single-phase fault; transmission lines;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering and Automation Conference (PEAM), 2012 IEEE
Conference_Location :
Wuhan
Print_ISBN :
978-1-4577-1599-0
Type :
conf
DOI :
10.1109/PEAM.2012.6612429
Filename :
6612429
Link To Document :
بازگشت