    Ground fault current protection of a 480Y/277V power system compliance with NEC design requirements

  • Author

    Dev Paul, P.E. ; Chavdarian, Peniamin Ben R.

  • Author_Institution
    AECOM, Oakland, CA, USA
  • fYear
    2013
  • fDate
    23-25 Sept. 2013
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    The NEC requires that a ground-fault protection of equipment be added when the building service disconnecting rating becomes 1000A or higher. To meet such a requirement, generally, the main service breaker is specified with ground-fault protection capability. This type of breaker provides ground-fault protection to equipment on the load-side of the main breaker, but does not provide protection for a ground-fault on the line-side of the main service breaker. Such a ground-fault may be on the service feeder connections at the main breaker or at the building service transformer. This paper provides a ground-fault protection relay scheme that can provide desired ground-fault protection of the building service feeders. Discussion on the building switchboard bus-rating, when a photovoltaic (PV) ac inverter has connection to the switchboard per NEC 705. 12. is also included.
  • Keywords
    arcs (electric); earthing; relay protection; building service feeders; ground fault current protection; ground-fault protection relay scheme; switchboard bus-rating; voltage 277 V; Buildings; Circuit faults; Inverters; Power supplies; Power transformers; Relays; Switches; Arcing fault; disconnect-switch; fault resistance; ground-fault damage; ground-fault protection relay;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Technical Conference (PCIC), 2013 Record of Conference Papers Industry Applications Society 60th Annual IEEE
  • Conference_Location
    Chicago, IL
  • ISSN
    0090-3507
  • Print_ISBN
    978-1-4673-5108-9
  • Type

    conf

  • DOI
    10.1109/PCICon.2013.6666056
  • Filename
    6666056