DocumentCode
648262
Title
Metrological determination of the frequency response of inductive voltage transformers up to 20 kHz
Author
Buchhagen, Christoph ; Fischer, M. ; Hofmann, Lutz ; Daumling, Holger
Author_Institution
Inst. of Electr. Power Syst., Leibniz Univ. Hannover, Hannover, Germany
fYear
2013
fDate
21-25 July 2013
Firstpage
1
Lastpage
5
Abstract
The use of power electronics and other assets with a nonlinear impedance characteristic causes harmonics in the electrical grid which should be monitored to keep the power quality at a high level. System operators connect their secondary equipment mainly to inductive voltage transformers that may have resonances in the frequency range of interest. Therefore, the influence of a voltage transformer itself on the PQ measurement has to be assessed, especially since they have some advantages compared to other technologies. Thereby, it is important to be able to measure the frequency response with a low measurement error. As shown in this work, several external factors can influence the measurement results to a great extent. Therefore, it should be known which variables affect the frequency behavior. Several influences are analyzed in this work and their impact on the frequency response is displayed.
Keywords
frequency response; measurement errors; potential transformers; power supply quality; PQ measurement; frequency response metrological determination; inductive voltage transformers; low measurement error; Cable shielding; Frequency measurement; Frequency response; Resonant frequency; Temperature measurement; Voltage measurement; Voltage transformers; Frequency response; Instrument transformers; Measurement errors; Voltage transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location
Vancouver, BC
ISSN
1944-9925
Type
conf
DOI
10.1109/PESMG.2013.6672835
Filename
6672835
Link To Document