DocumentCode
66813
Title
A Novel Approach to Utilize PLC to Detect Corroded and Eroded Segments of Power Transmission Lines
Author
Hamidi, R. Jalilzadeh ; Hosseinian, Seyed Hossein ; Sadeghi, Seyed Hossein Hesamedin ; Zhihua Qu
Author_Institution
Electr. Eng. Dept., Amirkabir Univ. of Technol., Tehran, Iran
Volume
30
Issue
2
fYear
2015
fDate
Apr-15
Firstpage
746
Lastpage
754
Abstract
A great number of existing power transmission lines have aged throughout the world. A considerable proportion of them are located in the environments that exacerbate their corrosion and erosion process. In-time detection of defects necessitates the use of nondestructive testing (NDT) techniques. Scanning the lines with robots and helicopters are the methods in use. In this paper, we propose a new NDT technique that uses the elements of power-line carriers, generally for information communication purposes, to detect the possibly corroded and eroded segments of each phase along a transmission line. The proposed NDT technique is based on the backward-wave propagation produced by a change in the characteristic impedance of a power transmission line, resulting from corrosion and erosion. To demonstrate the viability of the proposed approach, “EMTPWorks” is used to perform simulations. It is shown that the proposed technique can locate the surface defects and estimate the severity of them in transmission line conductors.
Keywords
conductors (electric); corrosion; helicopters; nondestructive testing; power cables; power transmission lines; robots; EMTPWorks; NDT technique; PLC Utilization; backward-wave propagation; characteristic impedance; corrosion segment detection process; defect in-time detection; erosion segment detection process; helicopters; information communication purposes; line scanning; nondestructive testing techniques; power transmission line conductors; power-line carrier elements; robots; surface defect location; Conductivity; Conductors; Corrosion; Couplings; Impedance; Poles and towers; Power transmission lines; Conductor aging; corrosion; erosion; nondestructive testing (NDT); power-line carrier (PLC);
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2014.2326167
Filename
7042362