• DocumentCode
    674292
  • Title

    Parametric analysis of overvoltages caused by back-flashover in “Siah-bishe” 400kV GIS substation

  • Author

    Babaei, Mehdi ; Babaei, Mehdi ; Niasati, Mohsen

  • Author_Institution
    High Voltage Design Dept., Faraniroo Eng. Co., Tehran, Iran
  • fYear
    2013
  • fDate
    2-4 Oct. 2013
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents the way of implementation of transient modeling concepts which are fully analyzed in referred standards, for the purpose of evaluating the lightning performance of studied system caused by back-flashover. In this regard, the impact of several parameters on lightning behavior of the system has been studied. The focus of this paper is on the lightning study of “Siah-bishe” 400kV gas insulated substation (GIS) and practical application of the study to the insulation design of this substation as a substation with a distinctive arrangement of equipment. This practical application has been rarely done before. The study was carried out by modeling all pieces of equipment in EMTP-RV and careful consideration of different modeling guidelines and instructions described in available standards.
  • Keywords
    flashover; gas insulated substations; EMTP-RV; Siah-bishe GIS substation; back-flashover; gas insulated substation; insulation design; lightning behavior; overvoltages; parametric analysis; transient modeling concepts; voltage 400 kV; Analytical models; Cable insulation; Electric potential; Flashover; Insulators; Lead; Magnetic analysis; EMTP; Lightning overvoltage; back flashover; cable; contingency condition; gas insulated substation; lightning arrester; lightning stroke;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power and Energy Conversion Systems (EPECS), 2013 3rd International Conference on
  • Conference_Location
    Istanbul
  • Print_ISBN
    978-1-4799-0687-1
  • Type

    conf

  • DOI
    10.1109/EPECS.2013.6713049
  • Filename
    6713049