• DocumentCode
    674346
  • Title

    A study on the overheating of the power cable tray

  • Author

    Hyung-Joo Choi ; Heung-Ho Lee

  • Author_Institution
    Dept. of Electr. Eng., Korea Midland Power Co. (KOMIPO), Seoul, South Korea
  • fYear
    2013
  • fDate
    26-29 Oct. 2013
  • Firstpage
    812
  • Lastpage
    817
  • Abstract
    This paper includes the results of the electromagnetic finite element analysis with regard to overheating problem of the power cable tray due to asymmetric magnetic flux density. This phenomenon was experienced in the utility power plant, Korea. The influences of the power cable arrangements and material of the tray were analyzed to find the best solutions using the eddy current-thermal coupled analysis.
  • Keywords
    finite element analysis; magnetic flux; power cables; power plants; Korea; asymmetric magnetic flux density; eddy current-thermal coupled analysis; electromagnetic finite element analysis; power cable tray overheating problem; utility power plant; Conductors; Core loss; Equations; Magnetic flux density; Materials; Mathematical model; Power cables;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines and Systems (ICEMS), 2013 International Conference on
  • Conference_Location
    Busan
  • Print_ISBN
    978-1-4799-1446-3
  • Type

    conf

  • DOI
    10.1109/ICEMS.2013.6713157
  • Filename
    6713157