A novel stator earth fault protection for large generator based on fault current
Author
Yuxue Wang ; Xianggen Yin ; Zhe Zhang ; Zhenxing Li
Author_Institution
State Key Lab. of Adv. Electromagn. Eng. & Technol., Huazhong Univ. of Sci. & Technol., Wuhan, China
fYear
2013
fDate
2-5 Sept. 2013
Firstpage
1
Lastpage
6
Abstract
A stator earth fault protection scheme based on fault current is presented in this paper. It trips out the faulted generator only if the fault current following the breakdown channel exceeds the tolerance capacity of the generator. Otherwise, it will just emit alarm signals. This protection scheme can avoid unnecessary trip-out of large generator, which influences the safe operation of power system, while ensuring the generator security. To achieve the scheme, methods of calculating fault current in real time are provided for three common generator neutral earthing methods basing on the zero-sequence equivalent circuits. An implementation scheme is given on the basis of the sub-harmonic injection protection device. The protection algorithm flow and protection criterion are discussed as well. Simulation results show the accuracy of the fault current calculation method and the validity of the protection scheme.
Keywords
earthing; equivalent circuits; power system faults; power system protection; power system security; stators; alarm signals; breakdown channel; fault current; faulted generator; generator security; neutral earthing; power system; stator earth fault protection; subharmonic injection protection; tolerance capacity; zero-sequence equivalent circuits; Circuit faults; Earth; Fault currents; Generators; Grounding; Stator windings; Earth fault; large generator; protection; stator; sub-harmonic injection;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Conference (UPEC), 2013 48th International Universities'
Conference_Location
Dublin
Type
conf
DOI
10.1109/UPEC.2013.6715036
Filename
6715036
Link To Document