679669
Title :
Underfloor air containment
Author :
Pervila, Mikko ; Kangasharju, Jussi
Author_Institution :
Dept. of Comput. Sci., Univ. of Helsinki, Helsinki, Finland
fYear :
2013
fDate :
29-31 Oct. 2013
Firstpage :
96
Lastpage :
101
Abstract :
This paper presents Underfloor air containment (UAC), a straightforward extension to Cold Aisle Containment (CAC). Both techniques aim to eliminate air stream mixing and thus reduce the volume of supply air needed for cooling. In UAC the underfloor air supply plenum of a data center is mechanically restricted to the floor sections containing the perforated tiles. We have implemented UAC in our department´s 110 kW, 74 m2 data center. Through experimental evaluation and per-tile air velocity measurements, we show that UAC improves the air velocities passing through the perforated tiles in the CAC by 9%. Our solution is light-weight, very low cost, and rapidly installable in other data centers.
Keywords :
air pollution; computer centres; air stream mixing elimination; cold aisle containment; data center; greenhouse gas emissions; perforated tiles; power 110 kW; underfloor air containment; underfloor air supply plenum; Aggregates; Cooling; Position measurement; Temperature measurement; Tiles; Velocity measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Online Conference on Green Communications (GreenCom), 2013 IEEE
Conference_Location :
Piscataway, NJ
Type :
conf
DOI :
10.1109/OnlineGreenCom.2013.6731035
Filename :
6731035
Link To Document :