Abstract
This paper uses State Estimation (SE) methods to validate transmission line parameters with Phasor Measurement Units (PMUs) at its ends. This exercise was needed prior to the commissioning of a new network voltage control strategy. Equations for the specific Hydro-Quebec´s measurements scheme are developed. Good behaviour of the algorithm is proven with simulations. The method is applied on a real line with real measurements. A bad data measurement is identified and eliminated. The system under study is then declared coherent.
Keywords
hydroelectric power stations; phasor measurement; power system parameter estimation; power system state estimation; power transmission lines; Hydro-Quebec measurement scheme; PMU measurement; SE method; network voltage control strategy; phasor measurement unit; state estimation method; transmission line parameter; Current measurement; Mathematical model; Measurement uncertainty; Phasor measurement units; Transmission line measurements; Voltage control; Voltage measurement;