DocumentCode
71579
Title
CT Saturation Detection Based on the Distance Between Consecutive Points in the Plans Formed by the Secondary Current Samples and Their Difference-Functions
Author
Santos, E. M dos ; Cardoso, G., Jr. ; Farias, P.E. ; de Morais, A.P.
Author_Institution
Technol. Center of Alegrete Dept., Fed. Univ. of Pampa (UNIPAMPA), Alegrete, Brazil
Volume
28
Issue
1
fYear
2013
fDate
Jan. 2013
Firstpage
29
Lastpage
37
Abstract
This paper proposes a novel method to detect the saturation intervals where the secondary current of current transformers for protection purposes becomes distorted. The method is based on the analysis of plans formed by the secondary current samples (i2) and their difference-functions (del[n]). The distance between consecutive points in these plans has a significant increase when saturation occurs, bucking the trend of the intervals without saturation. Two plans are considered: del[2] versus del[1] and del[3] versus del[2]. Besides the ease of implementation, the results indicate the effectiveness of the method to detect saturation intervals.
Keywords
current transformers; power transformer protection; CT; bucking; current transformer; difference function; power transformer protection; saturation interval detection; secondary current; Circuit faults; Distortion; Fault currents; Harmonic analysis; Impedance; Noise; Power system harmonics; Current transformer (CT); detection; protection; relays; saturation;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2012.2220382
Filename
6355978