Abstract
Different dynamic line rating systems have been developed in order to monitor lines and calculate the actual line rating. In this paper weather, conductor temperature and conductor tension based systems are analyzed. Measurements in two pilot lines were taken. One of them is the 66 kV evacuation line of a wind farm whereas, the other one is a 30 kV distribution line. In the analysis, actual rating values are calculated with the measurements of each system. Due to the fact that DLR results of the conductor temperature and conductor tension systems are inaccurate when differences between conductor temperature and ambient temperature are low, the analysis is made at different temperature ranges.
Keywords
conductors (electric); power distribution lines; power system measurement; wind power plants; DLR; ambient temperature; conductor temperature system; conductor tension system; dynamic line rating system performance; voltage 30 kV to 66 kV; wind farm distribution line; wind farm evacuation line monitoring; wind integration; Conductors; Temperature distribution; Temperature measurement; Temperature sensors; Wind speed; Ampacity; overhead lines; rating; real-time monitoring;
fLanguage
English
Publisher
ieee
Conference_Titel
Clean Electrical Power (ICCEP), 2015 International Conference on
Conference_Location
Taormina
Type
conf
DOI
10.1109/ICCEP.2015.7177548
Filename
7177548
Link To Document