DocumentCode
757229
Title
Influence of current transformer saturation on line current differential protection algorithms
Author
Gangadharan, P.K. ; Sidhu, T.S. ; Klimek, A.
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Western Ontario, London, Ont.
Volume
1
Issue
2
fYear
2007
fDate
3/1/2007 12:00:00 AM
Firstpage
270
Lastpage
277
Abstract
The performance of line current differential protection algorithms during current transformer (CT) saturation is analysed. The study covers popularly used algorithms and presents their degree of immunity to CT saturation. The degree of error in phasor measurement due to CT saturation is estimated through simulation studies and this information is used to decide the CT dimensioning for the relay
Keywords
current transformers; power transmission protection; relay protection; current differential protection algorithms; current transformer saturation;